Manual Call Point:

Manual Call Point consists of a micro switch, which, when pressed, can notify others of the occurrence of a fire in the environment.

Design Standards:

  • To be installed next to all exits and doors. 
  • Individuals should have access to one of these buttons within a distance of less than 45 meters from their location.
  • The distance between two buttons in wide or low-risk areas is 30 to 45 meters, and in narrow or high-risk areas, it is 15 to 25 meters.
  • The height of fire alarm buttons from the ground is 1.4 meters with an approximate tolerance of ±20 centimeters.